750Hz Ripple Signal Filter

Item Number: HNS030RF-750
Packaging Unit: 1 / each
  • Simple and easy to install (Size: 212 x 55 x 43mm)
  • Ripple signal flicker free with S-Click dimmers
  • Works with LED, halogen, CFL and incandescent lamps
  • Designed to fit through downlight hole
Sign In or Apply to view your price

Need More options? Contact Sales Or request a quote from your cart

Product Information

Product Description

Electricity suppliers for certain geographical areas of New South Wales and Queensland inject an off-peak ripple control signal onto their distribution networks in order to remotely control devices such as hot water systems. This allows for access to cheaper off-peak electricity, but can have an unfortunate effect on electrical appliances that are sensitive to the superimposed control signal.

Our HNS030RF ripple signal filter is a simple and easy-to-install solution to this problem, preventing the unwelcome effects of ripple signal events such as flickering LED lights or loud, buzzing fans. The ripple signal filter is a tuned passive inline filter which eliminates the superimposed ripple injection control signal from the normal mains supply to create a noise free filtered mains supply which can then be connected to the electrical appliances or light control systems. The device is designed to fit through a downlight hole and is compatible with LED, Halogen, CFL and Incandescent lamps.

With models available for 750Hz and 1050Hz frequency, we can supply an option to suit most affected areas.

Selecting a Ripple Signal Filter Frequency

The HNS030RF-750 ripple signal filter is tuned to eliminate ripple control signal frequency of 750Hz.

Use the HNS030RF-750 for areas of New South Wales that inject a 750Hz off-peak ripple control signal, such as Maitland, Bankstown, Sutherland, Sydney main load area and parts of Muswellbrook. Other regions of New South Wales, such as Newcastle, Dee Why and the Central Coast area, inject a 1050Hz ripple control signal frequency and will require a suitable filter model, see our part number HNS030RF-1050.

If in doubt about the ripple control signal for a particular location, always check with the service provider for confirmation before selecting a filter device.

Note: Our Ripple Signal Filters are not suitable for areas that use a ripple control signal of 492Hz, such as St George and some areas of Muswellbrook.

Operating Conditions

Supply Voltage: 230-240Va.c. 50Hz
Output Voltage: Filtered 230-240Va.c. 50Hz
Power Rating: 250W
Frequency: 750Hz
Attenuation: -30dB Nominal
Operating Temperature: -10 to +50 degrees Celsius
Compliance Standard: AS/NZS 3100
Ingress Protection: IP20
Note: Operation at temperature, voltage or load outside of the specifications may cause permanent damage to the unit.

The HNS030RF is to be installed as part of a fixed wire electrical installation. By law such installations must be made by an electrical contractor or similarly qualified person. For further information and important safety warnings, refer to the product datasheet (see Additional Information).

Loading...
Write Your Own Review
You're reviewing:750Hz Ripple Signal Filter

Your ordered quantity for this item is more than what we have in stock.


Request a quote

List of Materials
Contact Details
Comment
Project Details

* State/Region

Would you like to add this website to your device home screen?